DATA  SHEET
Ecosine MaxFN3472
Ecosine Max, 400 VAC 60 Hz Full Performance Passive Harmonic Filters
19. Apr 2024
27. Feb 2020
Ecosine Max
  • Demonstrate best cost-performance ratio
  • Achieve 5% THDi for diode rectifier without DC-link choke and thyristor rectifier
  • Best-in-class partial load performance
  • Most compact open panel design for cabinet integration
  • Reliable and robust
  • Plug and play, ready to use
Technical Specifications

Nominal operating voltage

3x380 VAC to 415 VAC ±10%

Overload capability

1.6x rated current for 1 minute, once per hour

Operating frequency

60 Hz ±1 Hz

Total harmonic current distortion THDi*

<5% @ rated power for drives without Ldc
~3.5% @ rated power for drives equipped with 4% Ldc

Total demand distortion TDD

According to IEEE 519

Nominal motor drive input power rating

280 to 480HP

High potential test voltage

P -> E 2520 VAC (1s)

Earthing system

TN, TT, IT

Efficiency

>99% for rated voltage and power

Overvoltage category

OV III (IEC 60664-1)

Temperature range (operation and storage)

–25°C to +40°C fully operational
+40°C to +70°C derated operation****
–25°C to +85°C transport and storage

Cooling

External cooling***

Protection category

IP 00

Flammability corresponding to

UL 94 V-2

Design corresponding to

Filter: UL 61800-5-1, EN 61800-5-1
Chokes: EN 60076-6

SCCR**

100 kA (UL approved)

MTBF (Mil-HB-217F)

>200,000 h @ 40°C/400 V


Approvals & Compliances

Features and Benefits

Schaffner ecosine harmonic filters represent an economical solution to the challenge of load-applied harmonics mitigation in three-phase power systems. With a plug-and-play approach and more compact dimensions than comparable products, they can be quickly installed and easily commissioned. They increase the reliability and service life of electric installations, help utilize electric sytem capacity better, and are the key to meet Power Quality standards such as IEEE 519. Ecosine filters reshape your distorted current back to the desired sinusoidal waveform. Schaffner ecosine filters can be applied to virtually any kind of power electronics with front-end six-pulse rectifiers, 3-phase diode or thyristor bridges, where harmonic current distortion needs to be reduced to defined limits.

Typical Applications

  • Equipment with front-end six-pulse rectifier
  • Motor drives
  • Factory automation equipment
  • Water/wastewater treatment facilities
  • Fan and pump applications
  • HVAC installations
  • Mission-critical processes
  • DC fast chargers

Typical electrical schematic

Filter selection table with circuit breaker module

Filter Rated load power @ 380 V/60 Hz Motor drive input current* Rated filter input current Typical power losses @ 40°C Circuit breaker rated current Weight
 
Terminal Frame size
  [kw] [HP] [Arms] [Arms] [W] [A] [kg] [lbs]    
FN3472-280-99-E0XXSXX 209 280 472 327 2832 200 245 540 Busbar S10
FN3472-315-99-E0XXSXX 235 315 537 375 3200 200 270 595 Busbar S10
FN3472-355-99-E0XXSXX 265 355 595 420 3451 250 295 650 Busbar S10
FN3472-400-99-E0XXSXX 300 400 656 469 3404 250 320 705 Busbar S12
FN3472-480-99-E0XXSXX 358 480 773 563 4173 300 385 849 Busbar L10

*    Motor drive input current without harmonic filter.

 

 

Filter selection table with trap disconnect jumper

Filter Rated load power @380 V/60 Hz Motor drive input current* Rated filter input current Typical power losses @ 40°C Weight
 
Terminal Frame size
  [kw] [HP] [Arms] [Arms] [W] [kg] [lbs]    
FN3472-280-99-E0XXJXX 209 280 472 327 2832 245 540 Busbar S10
FN3472-315-99-E0XXJXX 235 315 537 375 3200 270 595 Busbar S10
FN3472-355-99-E0XXJXX 265 355 595 420 3451 295 650 Busbar S10
FN3472-400-99-E0XXJXX 300 400 656 469 3404 320 705 Busbar S12
FN3472-480-99-E0XXJXX 358 480 773 563 4173 385 849 Busbar L10

*    Motor drive input current without harmonic filter.

 

 

Earth terminals

Earth (PE) Screw thread Screw torque
 

 

 

 

 

[Nm]

 

 

[lbs.in]

S08-L12

M12

       20-25 177-221

Frame size designation

Product selector

Filter configurations

E0XXSXX


- For rectifiers without DC-link
  choke

- Filters contain trap disconnect
  switch

E0XXJXX


- For rectifiers without DC-link
  choke

- Filters contain trap disconnect
  jumper

Mechanical data of IP 20 enclosure

Dimensions in mm

 Frame size*

W D H R S1 S2 S3 T LINE LOAD Recommended
cabinet size
WxDxH
S08 max. 650 max. 505 1120 380 330 230 490 13.5 255 ± 10 470 ± 30 800x600x2000
S10 890 max. 505 1120 370 514 n/a 280 13.5 255 ± 10 240 ± 30 1000x600x2000
S12 1060 max. 505 1120 370 684 n/a 280 13.5 255 ± 10 230 ± 10 1200x600x2000
L08 max. 680 557 1320 458 320 225 485 13.5 290 ± 10 540 ± 30 800x600x2000
L10 890 max. 557 1320 455 504 n/a 285 13.5 290 ± 10 230 ± 10 1000x600x2000
L12 1060 max. 557 1320 455 674 n/a 285 13.5 290 ± 10 220 ± 10 1200x600x2000

*   General tolerance: ISO 2768-v

Dimensions in inches

 Frame size*

W D H R S1 S2 S3 T LINE LOAD Recommended
cabinet size
WxDxH
S08 max. 25.6 max. 19.88 44.09 14.96 12.99 9.06 19.29 0.53 10.04 ± 0.039 18.5 ± 1.18 31.5x23.6x78.7
S10 35.04 max. 19.88 44.09 14.57 20.24 n/a 11.02 0.53 10.04 ± 0.039 9.45 ± 1.18 39.4x23.6x78.7
S12 41.73 max. 19.88 44.09 14.57 26.93 n/a 11.02 0.53 10.04 ± 0.039 9.06 ± 0.39 47.2x23.6x78.7
L08 max. 26.8 21.93 51.97 18.03 12.60 8.86 19.09 0.53 11.42 ± 0.039 21.26 ± 1.18 31.5x23.6x78.7
L10 35.04 max. 21.93 51.97 17.91 19.84 n/a 11.22 0.53 11.42 ± 0.039 9.06 ± 0.39 39.4x23.6x78.7
L12 41.73 max. 21.93 51.97 17.91 26.54 n/a 11.22 0.53 11.42 ± 0.039 8.66 ± 0.39 47.2x23.6x78.8

*   General tolerance: ISO 2768-v

Inlet air flow required for cooling

Frame size Min air volume*
 

 

[m3/h]

 

 

 CFM [ft3/min]

S08, L08 1069 629
S10, L10 1069 629
S12, L12 1069 629

*    Complete cooling requirement, including air inlet placement, must be followed. Please consult the user manual.

Headquarters, Global Innovation and Development

Switzerland
Schaffner Group
Industrie Nord
Nordstrasse 11e
4542
Luterbach
+41 32 681 66 26
info@schaffner.com

To find your local partner within Schaffner‘s global network schaffner.com

© 2024 Schaffner Group

The content of this document has been carefully checked and understood. However, neither Schaffner nor its subsidiaries assume any liability whatsoever for any errors or inaccuracies of this document and the consequences thereof. Published specifica-tionsw are subject to change without notice. Product suitability for any area of application must ultimately be determined by the customer. In all cases, products must never be operated outside their published specifications. Schaffner does not guarantee the availability of all published products. This disclaimer shall be governed by substantive Swiss law and resulting disputes shall be settled by the courts at the place of business of Schaffner Holding AG. Latest publications and a complete disclaimer can be downloa-ded from the Schaffner website. All trademarks recognized.

 

Sales and Application Centers

Switzerland
Schaffner EMV AG
Industrie Nord
Nordstrasse 11e
4542
Luterbach
+41 32 681 66 26
switzerlandsales@schaffner.com

China
Beijing Jingzhe Electronics Co.,Ltd.
Room 307, Building A, Jiahua Building, No.9 Shangdi 3rd Street, Haidian District
Beijing Yiting Ying
China
+86 13810880767
yingyiting@bjjingzhe.com

Singapore
Schaffner EMC Pte Ltd.
Blk 3015A Ubi Road 1 #05-09 Kampong Ubi Industrial Estate
408705
Singapore
+65 63773283
singaporesales@schaffner.com