Technical Specifications

Nominal operating voltage

3x380 VAC to 415 VAC ±10%

Overload capability

1.6x rated current for 1 minute, once per hour

Operating frequency

60 Hz ±1 Hz

Total harmonic current distortion THDi*

<8% @ rated power for drives without Ldc
<5% @ rated power for drives equipped with 4% Ldc

Total demand distortion TDD

According to IEEE 519

Nominal motor drive input power rating

280 to 480 HP

High potential test voltage

P -> E 2520 VAC (1s)

Earthing system

TN, TT, IT

Efficiency

>99% for rated voltage and power

Overvoltage category

OV III (IEC 60664-1)

Temperature range (operation and storage)

–25°C to +40°C fully operational
+40°C to +70°C derated operation****
–25°C to +85°C transport and storage

Cooling

External cooling***

Protection category

IP 00

Flammability corresponding to

UL 94 V-2

Design corresponding to

Filter: UL 61800-5-1, EN 61800-5-1
Chokes: EN 60076-6

SCCR**

100 kA (UL approved)

MTBF (Mil-HB-217F)

>200,000 h @ 40°C/400 V


Approvals & Compliances

Features and Benefits

Schaffner ecosine harmonic filters represent an economical solution to the challenge of load-applied harmonics mitigation in three-phase power systems. With a plug-and-play approach and more compact dimensions than comparable products, they can be quickly installed and easily commissioned. They increase the reliability and service life of electric installations, help utilize electric sytem capacity better, and are the key to meet Power Quality standards such as IEEE 519. Ecosine filters reshape your distorted current back to the desired sinusoidal waveform. Schaffner ecosine filters can be applied to virtually any kind of power electronics with front-end six-pulse rectifiers, 3-phase diode or thyristor bridges, where harmonic current distortion needs to be reduced to defined limits.

Typical Applications

  • Equipment with front-end six-pulse rectifier
  • Motor drives
  • Factory automation equipment
  • Water/wastewater treatment facilities
  • Fan and pump applications
  • HVAC installations
  • Mission-critical processes
  • DC fast chargers

Typical electrical schematic

Filter selection table with circuit breaker module

Filter                                               Rated load power @ 380 V/60 Hz Motor drive input current* Rated filter input current Required Ldc for 5% THDi** Typical power losses @ 40°C Circuit breaker rated current Weight
 
Terminal Frame size
  [kw] [HP] [Arms] [Arms] [mH] [W] [A] [kg] [lbs]    
FN3473-280-99-E0XXSXX 209 280 472 325 0.074 2085 200 220 485 Busbar S08
FN3473-315-99-E0XXSXX 235 315 537 374 0.066 2145 200 245 540 Busbar S08
FN3473-355-99-E0XXSXX 265 355 595 418 0.058 2382 250 270 595 Busbar S08
FN3473-400-99-E0XXSXX 300 400 656 467 0.052 2223 250 295 650 Busbar S08
FN3473-480-99-E0XXSXX 358 480 772 561 0.044 3057 300 360 794 Busbar L08

*     Motor drive input current without harmonic filter.
**    FN 3473 filters can be applied for drives with and without Ldc. 8% THDi (@ rated power) is achieved when FN 3473 is applied to drives without Ldc, while 5% THDi (@ rated power) is achieved when there is a 4% Ldc present in the drive.

 

 

Filter selection table with trap disconnect jumper

Filter                                               Rated load power @380 V/60 Hz Motor drive input current* Rated filter input current Required Ldc for 5% THDi** Typical power losses @ 40°C Weight
 
Terminal Frame size
  [kw] [HP] [Arms] [Arms] [mH] [W] [kg] [lbs]    
FN3473-280-99-E0XXJXX 209 280 472 325 0.074 2085 220 485 Busbar S08
FN3473-315-99-E0XXJXX 235 315 537 374 0.066 2145 245 540 Busbar S08
FN3473-355-99-E0XXJXX 265 355 595 418 0.058 2382 270 595 Busbar S08
FN3473-400-99-E0XXJXX 300 400 656 467 0.052 2223 295 650 Busbar S08
FN3473-480-99-E0XXJXX 358 480 772 561 0.044 3057 360 794 Busbar L08

*      Motor drive input current without harmonic filter.
**     FN 3473 filters can be applied for drives with and without Ldc. 8% THDi (@ rated power) is achieved when FN 3473 is applied to drives without Ldc,
        while 5% THDi (@ rated power) is achieved when there is a 4% Ldc present in the drive.

 

 

Earth terminals

Earth (PE)Screw threadScrew torque
 

 

 

 

 

[Nm]

 

 

[lbs.in]

S08-L12

M12

       20-25177-221

Frame size designation

Product selector

Filter configurations

E0XXSXX


- For rectifiers without DC-link
  choke

- Filters contain trap disconnect
  switch

E0XXJXX


- For rectifiers without DC-link
  choke

- Filters contain trap disconnect
  jumper

Mechanical data of IP 00 enclosure

Dimensions in mm

Frame size*

W D H R S1 S2 S3 T LINE LOAD Recommended
cabinet size
WxDxH
S08 max. 650 max. 505 1120 380 330 230 490 13.5 255 ± 10 470 ± 30 800x600x2000
S10 890 max. 505 1120 370 514 n/a 280 13.5 255 ± 10 240 ± 30 1000x600x2000
S12 1060 max. 505 1120 370 684 n/a 280 13.5 255 ± 10 230 ± 10 1200x600x2000
L08 max. 680 557 1320 458 320 225 485 13.5 290 ± 10 540 ± 30 800x600x2000
L10 890 max. 557 1320 455 504 n/a 285 13.5 290 ± 10 230 ± 10 1000x600x2000
L12 1060 max. 557 1320 455 674 n/a 285 13.5 290 ± 10 220 ± 10 1200x600x2000

*   General tolerance: ISO 2768-v

Dimensions in inches

Frame size*

W D H R S1 S2 S3 T LINE LOAD Recommended
cabinet size
WxDxH
S08 max. 25.6 max. 19.88 44.09 14.96 12.99 9.06 19.29 0.53 10.04 ± 0.039 18.5 ± 1.18 31.5x23.6x78.7
S10 35.04 max. 19.88 44.09 14.57 20.24 n/a 11.02 0.53 10.04 ± 0.039 9.45 ± 1.18 39.4x23.6x78.7
S12 41.73 max. 19.88 44.09 14.57 26.93 n/a 11.02 0.53 10.04 ± 0.039 9.06 ± 0.39 47.2x23.6x78.7
L08 max. 26.8 21.93 51.97 18.03 12.60 8.86 19.09 0.53 11.42 ± 0.039 21.26 ± 1.18 31.5x23.6x78.7
L10 35.04 max. 21.93 51.97 17.91 19.84 n/a 11.22 0.53 11.42 ± 0.039 9.06 ± 0.39 39.4x23.6x78.7
L12 41.73 max. 21.93 51.97 17.91 26.54 n/a 11.22 0.53 11.42 ± 0.039 8.66 ± 0.39 47.2x23.6x78.8

*   General tolerance: ISO 2768-v

Inlet air flow required for cooling

Frame size Min air volume*
 

 

[m3/h]

 

 

 CFM [ft3/min]

S08, L08 1069 629
S10, L10 1069 629
S12, L12 1069 629

*  Complete cooling requirement, including air inlet placement, must be followed. Please consult the user manual.

Headquarters, Global Innovation and Development

Switzerland
Schaffner Group
Industrie Nord
Nordstrasse 11e
4542
Luterbach
+41 32 681 66 26
info@schaffner.com

To find your local partner within Schaffner‘s global network schaffner.com

© 2024 Schaffner Group

The content of this document has been carefully checked and understood. However, neither Schaffner nor its subsidiaries assume any liability whatsoever for any errors or inaccuracies of this document and the consequences thereof. Published specifica-tionsw are subject to change without notice. Product suitability for any area of application must ultimately be determined by the customer. In all cases, products must never be operated outside their published specifications. Schaffner does not guarantee the availability of all published products. This disclaimer shall be governed by substantive Swiss law and resulting disputes shall be settled by the courts at the place of business of Schaffner Holding AG. Latest publications and a complete disclaimer can be downloa-ded from the Schaffner website. All trademarks recognized.

 

Sales and Application Centers

Switzerland
Schaffner EMV AG
Industrie Nord
Nordstrasse 11e
4542
Luterbach
+41 32 681 66 26
switzerlandsales@schaffner.com

China
Beijing Jingzhe Electronics Co.,Ltd.
Room 307, Building A, Jiahua Building, No.9 Shangdi 3rd Street, Haidian District
Beijing Yiting Ying
China
+86 13810880767
yingyiting@bjjingzhe.com

Singapore
Schaffner EMC Pte Ltd.
Blk 3015A Ubi Road 1 #05-09 Kampong Ubi Industrial Estate
408705
Singapore
+65 63773283
singaporesales@schaffner.com