LCL Filters FN6840

LCL Filter for Active Front End Motor Drives / Active Infeed Converter

FN6840

LCL Filter for Active Front End Motor Drives / Active Infeed Converter

  • Line side LCL filtering for AFE/AIC applications
  • Mandatory interface to connect the AFE/AIC-system to the grid
  • Helps to improve the power quality on the grid side
  • Reduces ripple currents and voltage distortions
  • All LCL components in one package
  • Compact design and ready to be connected

Features and Benefits

Improves the power quality for AFE (Active Front End) / AIC (Active Infeed Converter)
Effective attenuation of converter switching frequency to the grid/line side
Reduces the current and voltage ripples to acceptable levels for the grid/line side
Version with passive RLC damping module for system stability
Compact and user friendly design for ease of installation

Typical Applications

Hoists and cranes
Elevators
Test stands
Winder/Unwinder
Multiple motor drive systems with AFE/AIC
Motor drives and -systems with braking energy
Special machines with high inertia
Centrifuges
Transportation systems, e.g. chair lifts etc

Technical Specifications

Maximum continuous operating voltage

3×530 VAC

Nominal operating voltage

480 VAC

Rated currents

25A @ 50°C available

Other current ratings on request

25A @ 50°C available

Overload capability

1.6 x rated current for 1 min., ones per hour

Rated inductance L1 (grid/line side)

4% @ 400V, 50 Hz and rated current

Rated inductance L2 (inverter/converter side)

8% @ 400V, 50 Hz and rated current

Switching frequency

fPWM min. 3 kHz up to max. 10 kHz

Creepage and clearance distances

According UL 61800-5-1

Temperature range (operation and storage)

-25°C to +50°C full operation

>50°C to 70°C derated operation

-25°C to 85°C storage and transportation

Protection category

IP00 (IP20 on request)

Flammability corresponding to

UL 94 V-0

Design corresponding to

Filter: UL61800-5-1, EN61800-5-1

Chokes: EN61558-2-20 or EN60076-6

Insulation class

EIS 200

* Note: for detailed resulting ripple current, please contact your local Schaffner office or partner.

Typical electrical schematic

FN6840

Approvals & Compliances

RoHS Label
CE Label
UKCA Label